Refrigerant Gases - HFC's

R410A

  • GWP: 2,088 IPCC 4th Revision
  • Application: A/C
  • Preferred Oil: POE
  • Ashrae Class: A1
  • Composition: 50% R32, 50% R125
Available Cylinder Sizes
9/20/46 Kg Cyl – 720 Kg Drum, ISO Tank

DESCRIPTION

Air Conditioning Unit R410AR410A was developed in 1991 by the Honeywell Corporation as a non-ozone depleting R22 replacement for air-conditioning systems.

R410A is a near azeotropic blend of 50% R32 and 50% R125 and has minimal glide.

An azeotrope is the name given to a blend of liquids that all have the same boiling temperature meaning that the separate components boil and condense at the same time.

Zeotropic blends have different boiling temperatures meaning that the separate components boil and condense at different temperatures, this can lead to the blend “fractionating”.

Fractionation is when one of the components boils faster or before the other components leading to the vapour or liquid going out of specification.

The “glide” is given to the term used to denote the difference in the boiling temperatures of the most and least volatile component.

R410A has a glide of approx. 0.5oC so both the R32 and R125 components both boil within a half degree of each other so when boiling and condensing both liquid and vapour stay at a 50/50% blend staying within its specification.

R410A can not be used with traditional mineral oils with equipment manufacturers recommending using a Polyolester oil.

R410A should not be used to retrofit existing R22 systems due to the higher pressure of R410A.

Air Conditioning Systems R410AR410A does have significant environmental issues, classed as an HFC (Hydrofluorocarbon) it does not contain chlorine so does not damage the ozone layer but it is however classed as a greenhouse gas so when released to the atmosphere R410A contributes towards global warming. This is measured by its global warming potential (GWP) which for R410A is 2,088.

To put that into context the benchmark is carbon dioxide (CO2) itself which has a GWP of just 1 making R410A over 2,000 time worse than CO2.

Because of the relatively high GWP of R410A new air-conditioning split systems now come with R32 as its component refrigerant. R32 has a much lower GWP of 675 and is much more environmentally friendly, though it is not without its problems. R32 has been classified as an A2L refrigerant making it mildly flammable so its use has been limited.

As R410A is made up of 50% R32 and 50% R125 the equipment can perform just as well using the R32 component and the R125 was primarily added to suppress its flammability.

Note that equipment designed to use R410A cannot be retrofitted with R32 as R410A equipment was not designed to be used with a flammable refrigerant.